Supplier
Supplier
AC input voltage range
3ψ 3W/ △196305VAC or 3ψ 4W/Y 340530VAC
AC inrush current (max.)
75A/230VAC(3ψ 3-wire / △) 50A/400VAC(3ψ 4-wire / Y)
Overload protection
100 ~ 107% of rated current
Protection type: Constant current limiting, unit will shut down after 5 seconds. re-power on to recover
Over-voltage protection
| 145 ~ 166V | 273 ~ 312V | 420 ~ 480V |
Protection type: Shut down o/p voltage, re-power on to recover
Over temperature protection
Shut down o/p voltage, recovers automatically after temperature goes down
Withstand voltage
I/P-O/P:4.3KVDC I/P-FG:2.8KVDC O/P-FG:2.8KVDC
Working temperature
-30 ~ +70 (Refer to "Derating Curve")
Safety standards
UL62368-1, CAN/CSA C22.2 , TUV BS EN/EN62368-1, EAC TP TC 004 approved
Dimension (LxWxH)
460x211x83.5mm