ES-SU3K3KVA Online UPS Double Conversion
Request special price above 200
Request a QuoteRequest special price above 200
Request a QuoteDatasheet (PDF)
The MEAN WELL ES-SU3K is a 3KVA/3KW true double-conversion online UPS available in tower and rack versions, with or without built-in batteries. It provides a pure sine wave output with an output power factor of 1, an input power factor of ≥0.99, low input current harmonics, ECO mode, EPO (emergency power off), USB/RS-232 communication and an LCD panel, with adjustable battery charging current. Output voltage: 200/208/220/230/240 VAC.
| Model | ES-SU3K |
| Brand | MEAN WELL |
| Topology | Online double conversion |
| Power | 3KVA/3KW |
| Input voltage | 110–300 VAC (load-dependent), 40–70 Hz |
| Output voltage | 200/208/220/230/240 VAC |
| Waveform (battery mode) | Pure sine wave |
| Battery | 72 V: external (TH/RH) or built-in 12V/9Ah × 6 (THB/RHB) |
| Transfer time | AC to battery 0 ms; online to bypass 4 ms typ. |
| Efficiency | AC mode 94%; ECO mode 97%; battery mode 91% |
| Operating temperature | 0–40 °C |
| Communication | RS-232 / USB |
| Display | LCD |
| Versions | ES-SU3K-TH (tower), -THB (tower, built-in battery), -RH (rack), -RHB (rack, built-in battery) |
| Weight | 7.4 kg (TH) / 26.2 kg (THB) / 10.5 kg (RH) / 26.7 kg (RHB) |
| Size | 426 × 190 × 338 mm (tower); 630 × 438 × 88 mm (rack) |
Official datasheet: ES-SU3K datasheet (PDF). Specifications are taken from the manufacturer's published datasheet and product page; refer to the datasheet for complete ratings, dimensions and installation details.